background image

B1 copy starts here

B2 copy starts here

B3 copy starts here

Headline starts here

Installation

Pre-installation requirements

3.  Wire routing (OEM) 

 

The length of wiring to the SPD must be kept at a minimum. 
For the best performance, ABB recommends maintaining 
36" of length or less for each conductor (including neutral 
and/or ground). Wire lengths should be short, straight runs 
between the SPD and power source. Wiring impedance can 
be further reduced by twisting the phase, neutral and 
ground conductors together and routing them in the same 
raceway or channel. Always avoid sharp bends when routing 
SPD connecting conductors.

4.  Circuit breaker (OEM) 

 

A dedicated circuit breaker is not required for TPME or  
TPHE models. If a dedicated branch breaker is to be used  
to connect the SPD to the power system, ABB recommends 
a 60 A or higher rated breaker.

5.  Remote alarm contacts  

Remote alarm monitoring contacts are provided on all  
SPD model types covered by this manual. If this type of 
monitoring is desired, refer to the following diagram for  
the location and pin configuration of these contacts. The 
contacts are dry, form C type, rated 120 V AC, 1 A (30 V DC,  
2 A) maximum. Once the SPD has been energized and is 
operating as intended, the alarm contacts will switch to 
“normal status.” The contacts will only change back to 
“alarm status” if there is a failure within the SPD 
suppression circuitry, or if power has been disconnected 
from the SPD. Allowing the remote alarm contacts remain 
unconnected will not affect the performance or integrity  
of the SPD.

6.  SPD disconnect switch  

Not provided on NSBX or NSWM models.

7.  Pre-energization check 

 

Once all of the pre-installation conditions have been met 
and the SPD has been installed, the SPD can now be 
energized. For SPD operational status, refer to Operation 
and Maintenance sections.

NOTICE

Hi-Leg Delta power systems:
TPME240H and TPHE240H SPD model types are intended for 
Hi-Leg Delta systems and are configured with Phase B as the 
intended Hi-Leg connection point. Attempting to connect the 
SPD Phase C or Phase A conductor to the system Hi-Leg will 
result in immediate SPD failure.


Power terminals and remote alarm locations

Phase C/line 3

Ground

Neutral

Phase B/line 2

Phase A/line 1

Normal status indication:
NO - COM = Closed
NC - COM = Open

Alarm status indication:
NO - COM = Open
NC - COM = Closed


The illustration above represents the SPD in a vertical orientation. Other orientations 
are possible depending on the type of equipment in which the SPD is installed. The  
SPD features will be the same regardless of application.

6

TPM E A N D TPH E N S BX A N D N SWM S E R I E S I NTEG R A L S PDS

Содержание TPME Series

Страница 1: ...umber suffixes of NSBX and NSWM Example TPHE277Y20NSBX Model types are also available with a UL Type 1 rating These models will be labeled with the part number suffix of T1 INSTALLATION OPER ATION AND MAINTENANCE MANUAL TPME and TPHE NSBX and NSWM series Integral SPDs for OEM factory installation ...

Страница 2: ...igueur dans le pays lieu où l appareil est utilisé WARNING Do not HIPOT the SPD unit or the electrical system to which the SPD unit is connected without disconnecting the SPD unit s conductors including phases neutral and ground Ne procédez PAS à des ESSAIS DE RIGIDITÉ DIÉLECTRIQUE sur le SPD ou le système électrique auquel il est connecté sans déconnecter les conducteurs des SPD y compris les pha...

Страница 3: ... diagram EXAMPLE OF AN NEC COMPLIANT GROUNDING ARRANGEMENT FOR A SEPERATELY DERIVED SYSTEM for an example of an installation that complies with these NEC recommendations Verify that there have not been multiple instances of neutral to ground bonds on the electrical system These bonds while either intentional or accidental result in ground currents that can create differential voltage potentials be...

Страница 4: ...se 3 wire ground TPME TPHE120Y TPME TPHE220Y TPME TPHE240Y TPME TPHE277Y TPME TPHE347Y 120 208 V 220 380 V 240 415 V 277 480 V 347 600 V 150 V L N L G 320 V L N L G 320 V L N L G 320 V L N L G 420 V L N L G Three phase WYE 4 wire ground TPME TPHE 240D TPME TPHE 480D 240 V 480 V 270 V L G 550 V L G Three phase Delta 3 wire Three phase WYE 3 wire TPME TPHE 240H 120 240 V 150 V L N L G Phase A C 270 ...

Страница 5: ...raîner des blessures graves la mort et ou des dégâts matériels The SPDs described in this manual are intended to arrive at the job site as factory mounted and wired into OEM electrical panels or gear When receiving the SPD on site as OEM factory preinstalled please begin at step number 5 below Installation steps 1 4 shown below appended with OEM are intended to provide guidance to OEMs for factory...

Страница 6: ...ts will switch to normal status The contacts will only change back to alarm status if there is a failure within the SPD suppression circuitry or if power has been disconnected from the SPD Allowing the remote alarm contacts remain unconnected will not affect the performance or integrity of the SPD 6 SPD disconnect switch Not provided on NSBX or NSWM models 7 Pre energization check Once all of the ...

Страница 7: ...cators will be illuminated green There is one green indicator per each protected phase 2 Alarm status indicator LEDs When illuminated the red alarm status indicator LED will provide notification of an SPD failure condition Verify the alarm status indicator is not illuminated upon startup 3 Remote alarm contacts Remote alarm contacts are available to remotely monitor the health status of the SPD An...

Страница 8: ...ust be replaced En cas de condition d alarme du SPD n essayez pas de démonter le SPD pour remplacer les fusibles ou d autres composants Le SPD contient des MOV protégés thermiquement qui ne s ouvrent que lorsque le SPD tombe en panne et ne fonctionne plus L ensemble du SPD doit être remplacé 4 Test enable disable switch cont Test position The test switch provides a quick diagnostic status of the a...

Отзывы: