IS--1627

IS--252LRJS--IEC

Revision: 0

Page 5 of 5

STEP 6 CONNECT ELBOW AND BUSHING PLUG

1.

Clean the receptacle portion of the elbow connector and the mating bushing and lubricate with the lubricant supplied.

LUBRICATE ONLY IF THE TRANSFORMER AND ELBOW ARE KNOWN TO BE DE--ENERGIZED.

2.

Use a fully insulated hot stick to place the elbow on the bushing. DO NOT OPERATE BY HAND. DO NOT SEPARATE IF

ENERGIZED.

Hotstick

Clean and Lubricate only if known to be de--energized

STEP 7

BAIL ELBOW

1.

Pull hold--down bail up over the crown or top of elbow

so that the eyebolt on the bail is directly over the

operating eye.

2.

Tighten down on elbow locator by turning eyebolt in a

clockwise direction. Adjust the nut on the eyebolt

until it allows the eyebolt to seat securely in the locator.

The nut should act as a stop to prevent the eye

bolt from applying excessive force on the elbow. Once

the nut is in final position, it will not have to be

readjusted when removing and replacing elbow.

Operating Eye

VOLTAGE TEST

ELASTIMOLD connectors equipped with an integral capacitance test point can be used to establish whether or not the

circuit is energized. When using the test point, complete the following steps:

1.

Remove test point cap with a hotstick. When removing cap, PEEL OFF AT AN ANGLE rather than pulling directly in line

with the test point assembly.

2.

WARNING:

THE VOLTAGE TEST POINT IS A CAPACITANCE DEVICE, IT IS NOT DIRECTLY CONNECTED TO THE

CONDUCTOR. Do not use conventional voltage measuring equipment. Follow the manufacturer’s directions for the

meter that is used. Test with a suitable sensing device, made for use with separable connectors manufactured with

capacitive test points, to determine if cable is energized. Contamination, moisture, dirt, etc. around the test point or use

of the wrong measuring equipment can provide a false “no voltage” indication on an energized elbow. To prevent

serious or fatal injury treat the elbow as energized until the “no voltage” test point indication is confirmed by other means.

3.

After voltage detection has been made, clean the inside surface of the cap and lubricate with lubricant supplied;

replace it on the test point.

THOMAS & BETTS CORP. PROPRIETARY AND CONFIDENTIAL

BY ACCEPTANCE OF THIS DOCUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION CONTAINED IN IT, AS WELL AS THE

SUBJECT MATTER AND ALL PROPRIETARY AND NOVEL FEATURES DISCLOSED, ARE OWNED BY THOMAS & BETTS CORPORATION (”THE COMPANY”

AND A MEMBER OF THE ABB GROUP) AND THAT DEVICES EMBODYING SUCH FEATURES OR INFORMATION DERIVED FROM THESE DRAWINGS WILL

NOT BE MANUFACTURED BY OR FOR YOU OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTEN CONSENT OF THE COMPANY.

THESE DRAWINGS ARE NOT TO BE COPIED OR REPRODUCED OR DISCLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTEN CONSENT OF

THE COMPANY. ALL DRAWINGS AND INFORMATION ARE TO BE RETURNED TO UPON DEMAND OR UPON COMPLETION OF PURPOSE FOR WHICH

LENT. COPYRIGHT THOMAS & BETTS CORP. ALL RIGHTS RESERVED. ALL OTHER TRADEMARKS ARE THE PROPERTY OF THEIR RESPECTIVE

OWNERS.

Содержание Thomas & Betts Elastimold 252LRJS-IEC

Страница 1: ...assembled product may result in its failure FOR MORE INFORMATION ON PARTS INSTALLATION RATINGS AND COMPATIBILITY CALL THE NEAREST ELASTIMOLD OFFICE Limited Warranty 1 T B warrants that its products will be free from defects in materials or workmanship for a period of two 2 years except for tools which are warranted separately seewarranty accompanying those products Fisher Pierce products and Elast...

Страница 2: ...ip of mastic if needed to build up the outer diameter in the area of the first mastic location Cover all mastic with vinyl tape 4 Remove insulation shield and insulation from the cable end Cut squarely taking care not to nick conductor 5 Wire brush bare aluminum conductors and immediately place compression lug over bushing Rotate to spread inhibitor Position compression lug so the CONTACT THREADED...

Страница 3: ...solder block of braid is centered on top of the mastic tape 8 Apply mastic over the braid as shown 9 Over wrap mastic with two half lapped layers of vinyl tape 10 Wrap the third piece of mastic around thecable entrance of the connector being used Over wrap mastic with two half lapped layers of vinyl tape Mastic Vinyl Tape 11 Remove insulation shield and insulation from the cable end Cut squarely t...

Страница 4: ...ten with wrench until wrench bends STEP 4 ASSEMBLE BAIL Place hold down bail in hold down bracket Bracket Compress Bail Insert into Brackets Bracket Optional Bail Locator STEP 5 CONCENTRIC NEUTRAL CONNECTION OR COPPER TAPE 1 Pull the hood over the concentric neutral seal area on the cable by pulling the tabs and or rolling the seal down 2 Using a separate copper wire No 14 AWG 2 5mm or equivalent ...

Страница 5: ...CTLY CONNECTED TO THE CONDUCTOR Do not use conventional voltage measuring equipment Follow the manufacturer s directions for the meter that is used Test with a suitable sensing device made for use with separable connectors manufactured with capacitive test points to determine if cable is energized Contamination moisture dirt etc around the test point or use of the wrong measuring equipment can pro...

Отзывы: