12.19
Cable specifications
12.19.1
AC input cable for the power cabinet
Parameter
Specification
Cores
4 cores, according to IEC 60446
Cross section range
177 mm² to 240 mm² (350 kcmil to 500
kcmil)
Conductor
Bare copper, fine wired, bunch stranded,
according to VDE 0295 Cl.5/IEC Cl.5
Cross section range for aluminum
240 mm² (500 kcmil)
Diameter of the phase conductors
Refer to the local rules.
Insulation
PVC that is serviceable for outdoor use,
UV-protected, and oil resistant
Minimum nominal voltage Uo/U
450/750 VAC
Minimum test voltage
4 kV
Ambient temperature range
-40 °C to +80 °C (-40 °F to +176 °F)
Diameter of the PE conductor
According to the local rules
12.19.2
DC power installation cables
The below data are specific for the DC power cables between the power cabinet and
the charge post.
Parameter
Specification
Type
DLO, Type W
2
2 DC cables per DC+ and 2 DC cables per
DC-
Flexible, with voltage sensing lines
Unshielded
Number of cores
1
Cross section range (minimum)
125 mm² (250 kcmil)
Cross section range (maximum)
300 mm² (592 kcmil)
Diameter
27 to 35 mm (1.1 to 1.4 in)
Maximum length
60 m (197 ft)
Conductor
Stranded in tin plated copper or alumi-
num
fine wire, according to VDE 0295 cl.5/IEC
Cl.5
Diameter of the phase conductors
Refer to the local rules.
Insulation
Rubber or PVC that is serviceable for
outdoor use, UV-protected, and oil re-
sistant
Voltage rating Uo
3
/U
4
1000 V
2
You can only use XHHW-2 cables after an approval of ABB EV Infrastructure.
3
Phase to ground nominal voltage
4
Phase to phase nominal voltage
Technical data
9AKK107992A3069-EN | 004