• Consult your local electrical codes for the correct wire size, based on the environment, the conductor type and
the rating of the EVSE
• The wire AWG is based on the copper wire type
Wire specifications
AC input mechnical lug
Strip length 0.55 in (14 mm), supported range 8 - 2 AWG (8.36 - 35 mm²)
AC input cold pressed ring terminal 80 A
Strip length 0.55 in (14 mm), 2 AWG (35 mm²)
AC input cold pressed ring terminal 40 A
Strip length 0.55 in (14 mm), 6 AWG (13 mm²)
PE cold pressed ring terminal
Strip length 0.33 in (8.5 mm), 8 AWG (8,36 mm²)
Terminal block, external meter, input and output
Strip length 0.19 in (5 mm), supported AWG range 24 - 12 (0.20 - 3,3 mm²)
Certification and standards
Safety standards
UL 2594, UL 2231-1, UL 2231-2, UL 1998, CSA C22.2. NO.280, NMX-J-667-ANCE
Codes and standards
FCC Part 15 Class B, ENERGY STAR
Certification
SGS
Warranty
24 months
AC input cable
Cable shielding (optional)
The local rules require shielded cables.
The cable shielding must be connected to the PE rail at the two ends of the cable
Diameter of the phase conductors
Refer to the local rules
Diameter of the PE conductor
The same as the diameter of the phase conductors