7.5
De-energize the EVSE
7.5.1
De-energize the EVSE - general procedure
Preliminary requirements
•
•
Voltage tester
Procedure
1. Open the front door and right doors. Refer to section
.
2. Set the manual switch to the
0 position (horizontal).
Warning:
General hazard
•
Be careful and use both your hands to turn the manual switch. The
manual switch turns quite arduous.
3. Wait until all the power modules are off:
•
All the LEDs of the power modules are off.
•
The fans have stopped.
4. Measure the AC voltage.
a. For 360, refer to section
b. For 180 and 60, refer to section
c. Make sure that all the measured voltages are 0 V.
5. Measure the DC voltage.
a. Refer to section
b. Make sure that all the measured voltages are 0 V.
6. Close the doors. Refer to section
.
7.5.2
Measure the AC voltage (Terra 360)
Preliminary requirements
•
•
Only do this procedure if
a different procedure refers
to this procedure.
•
Voltage tester
Maintenance and cleaning
9AKK108467A6398-EN | 002
87