Parameter
Function or specification
MV switch
Dedicated MV/LV transformer for indus-
trial use of the EVSE
For residential use of the EVSE you can
connect directly to low voltage public
grid
Automatic circuit breaker
Output 4 x 400 A, 690 Vac
Additional option: Residual current
breaker type B
Caution: A
residual
current
breaker
type B is
Mandatory
for an EVSE
with CHA-
deMO out-
put.
Output 4 x 400 A, gG Fuses, 690 Vac
Adjustable Idn 30 to 300 mA
10.20.3
External residual current device (Terra 60)
Id
A
B
C
D
E
A
3 Phase MV
B
MV switch
C
3 Phase + Neutral 400 Vac
D
Automatic circuit breaker
E
Residual Current Breaker Type B
Technical data
9AKK108467A6398-EN | 002
127