background image

Installation instructions
1.  Note: The circuit supplying mains power to the fitting must not be energised until installaton of 

the fitting is completed.

2.  Mark and cut-out a hole in the ceiling to suit either small or large Spitfire head. The cut-out size for 

the standard lamp head is 50mm. The cut-out size for a small 85mm adaptor plate is 70mm and for 
the large 141mm adaptor plate is 130mm. 

Note: The adaptor plates are mainly used for existing 

Spitfire replacement or where ceiling access is limited.

3.  Snap the lamp head to the appropriate adaptor plate (if used).
4.  Connect the battery to the control pack, the battery pack can be attached to the control pack using 

cable tie supplied.

5.  Connect the mains wiring brown to (active), blue to (neutral), white to (DALI +) and black to (DALI -), 

see figure 1.

6.  Feed the battery and control pack assembly through the ceiling cut-out and secure them to a 

suitable location within the ceiling space. If access to the ceiling cavity is not available, connect the 
mains power cord before recessing the battery and control pack in the ceiling cut-out. Secure the 
battery and control pack to a suitable location within the ceiling space.

7.  Check operation of the unit to ensure that the installation was successful. Once powered up, as a 

non-maintained fitting the present lamp stays off. Allow a few minutes to give the battery a small 
charge, then press the test button located at the Spitfire lamp head. Hold the test button in for a 
few seconds and observe the operation of the lamp switching from mains to the emergency mode. 
If the lamp on emergency mode works momentarily, that is okay. Try again in a few more minutes 
in case battery is completely discharge, it may take a little time to charge up enough to operate 
even momentarily. After this time, press the test button again and if the lamp does not work at all, 
check the supply, the connections and follow the instruction given in the trouble shooting guide at 
the end of this document. Operation modes of the LED status as shown below. In the pattern 
descriptor ‘_’ means off while ‘R’, ‘G’ and ‘Y’ mean red, green and yellow, respectively. 

Note: LED 

patterns are displayed only if mains is present. If there is a mains failure, the LEDs are turned 
off.

Priority

Pattern

Indicated condition

9

GG_

Damaged configuration, the unit is not operational

8

GG_R_

Hardware fault, the unit is not operational

7

G

The button is pressed

6

_

Faulty charger or battery, cannot go to emergency mode

5

RR__

Self-test is in progress

4

GG_R_R_

STM32 interface card is missing

3

GG_R_R_R_R_

The DALI bus is not powered

2

YY_Y_Y_Y_Y_Y__

Identify command was received from DALI

1

YY__

Last self test failed

1

YYYY_

Last self test succeeded

0

R

Unit is healthy, battery is charging

Important: 24 hours is required to allow the fitting battery to reach full capacity, ie: prior to a 
discarge test. As the installer, it is your responsibility to conduct the initial discharge testing of the 
fitting. Refer to AS/NZS 2293.

DALI emergency features

DALI emergency comprises most of the 
standard features of DALI in addition to 
features and commands specific to emergency 
products. Some of these are outlined below:

Rest
•  To ensure maximum battery life (especially 

through the construction stages), a smart 
control system can use the rest command to 
extinguish the emergency lamp (when 
power has been lost) and limits the number 
of continual charge and discharge cycles 
present in the commissioning or installation 
phase. This reduces the stress on the 
battery and ensures the longest possible 
life.

Function test
•  A test designed to quickly check the unit’s 

functionality. During this short test the unit 
is able to check that the battery, lamp and 
circuitry are all working correctly. The result 
of this test is stored and can be returned to 
the control system when required.

Duration test
•  The most important test for an emergency 

device is the duration test. This test allows 
the device to change to emergency mode 
and discharges the battery.

•  You will need to allow 24 hours for the 

battery to fully charge prior to conducting 
this test, presently (at the time of writing), 
the standard requires that fittings operate 
in emergency mode for a period not less 
than 2 hours for their commissioning test 
and for not less than 90 minutes thereafter 
(it is required that 6 monthly discharge tests 
be carried out). The result of the test is 
stored and can be returned to the control 
system when required.

Inhibit
•  Another measure that can be initiated by the 

control system is the inhibit feature which 
can stop the emergency DALI device from 
going into emergency mode. 

Prolong time
•  The prolong time function of the emergency 

DALI protocol gives installers the ability to 
prolong the emergency light’s emergency 
state. This time can be set from 0 to 60 
minutes and can ensure that a safe lighting 
level is present after a short power failure.

Removal instructions
1.  
Before removing the installed fitting, de-

energise and lock off the supply circuit.

2.  Disconnect the mains and DALI wiring 

connections.

3.  Disconnect the battery and lamp head plug.

Power cable

Main control unit

Brown - active
Blue - neutral
White - DALI +
Black - DALI -

Figure 1

Отзывы: