15
Remote reset input
switchgroup SGB
Switch
Function
Factory
setting
SGB/1
Remote reset of indicators
0
When SGB/1=0, the indicators are not reset by signal BS.
When SGB/1=1, the indicators are reset by signal BS.
SGB/2
Remote reset of indicators and output relays
0
When SGB/2=0, the indicators and output relays are not reset by
signal BS.
When SGB/2=1, the indicators and output relays are reset by
signal BS.
SGB/3
Remote reset of indicators, output relays and memorized values.
0
When SGB/3=0, the indicators, output relays and memorized values
are not reset by signal BS.
When SGB/3=1, the indicators, output relays and memorized values
are reset by signal BS.
SGB/4
Reserved for future use
0
SGB/5
Reserved for future use
0
SGB/6
Reserved for future use
0
SGB/7
Reserved for future use
0
SGB/8
Reserved for future use
0
Measured data
The measured values are shown by the three
right-most digits of the display. The currently
measured data are indicated by an illuminated
LED indicator on the front panel.
Indicator
Measured data
I
L1
Line current on phase L1 in ampere
I
L2
Line current on phase L2 in ampere
I
L3
Line current on phase L3 in ampere
I
0
Neutral current in ampere
∆
I
The actual value of phase unbalance in per cent of the highest phase current