background image

9

To be able to operate the relay needs a secured
auxiliary voltage supply. The power supply
module forms the voltages required by the meas-
uring relay module and the auxiliary relays. The
withdrawable power supply and output relay
module is located behind the system front panel,
which is fixed by means of four cross-slotted
screws. The power supply and output relay
module contains the power supply unit, all
output relays, the control circuits of the output
relays and the electronic circuitry of the external
control inputs.

The power supply and output relay module can
be withdrawn after removing the system front

panel. The primary side of the power supply
module is protected with a fuse, F1, located on
the PCB of the  module. The fuse size is 1 A
(slow).

The power supply  unit is a transformer con-
nected, i.e. galvanically isolated primary and
secondary side, flyback-type dc/dc converter.  It
forms the dc secondary voltages required by the
measuring relay module; that is +24 V, 

±

12 V

and +8 V. The output voltages 

±

12 V and +24

V are  stabilized in the power supply module,
while the +5 V logic voltage required by the
measuring relay module is formed by the stabi-
lizer of the relay module.

1 A slow

+8V

+12V

-12V

+24V

Uaux

80...265 V ac & dc

18...80 V dc

Unstabilized logics
voltage

Operation amplifier  
voltage

Output relay coil
voltage

Fig. 5.Voltage levels of the power supply module.

A green LED indicator U

aux

 on the system front

panel is illuminated when the power supply
module is in operation. The supervision of the
voltages supplying the electronics is placed in
the measuring module. If a secondary voltage
deviates from its rated too much, a self-supervi-
sion alarm will be established. An alarm is also
established when the power supply module is
withdrawn from the relay case, or when the
auxiliary power supply to the relay is inter-
rupted.

There are two versions of power supply and
output relay modules available. For both types,
the secondary  sides and the relay configur-
ations are identical, but the input voltage ranges
differ.

Voltage ranges of the power supply modules:
- SPTU 240R2 or
  SPTU 240R3

  U

aux

 = 80...265 V dc/ac

- SPTU 48R2 or
  SPTU 48R3

  U

aux

 = 18...80 V dc

The modules SPTU 240 R2 or SPTU 240 R3
can be used with both ac and dc voltages.
Modules SPTU 48 R2 and SPTU 48 R3 are
designed for dc supply only. The auxiliary volt-
age range of the power supply module of the
relay assembly is indicated on the system front
panel.

The module SPTU 240R2 and SPTU 48R2
have a normally open trip contact whereas the
modules SPTU 240R3 and SPTU 48R3 have a
normally closed trip contact.

Power supply
and output relay
module

Содержание SPAM 150 C

Страница 1: ...n I s 3I 3 I RS 641 Ser No SPAM 150 C Uaux SPCJ 4D34 REGISTERS OPER IND 0 0 0 0 0 1 2 3 4 5 6 7 8 n L3 n L1 n L2 1 2 3 4 5 6 7 8 o 2 5 9 EXT TRIP 9 t 955D I I I I I I I I I I I 80 265V 18 80V n I I 5A...

Страница 2: ...nitoring all three phases the thermal replica is adjustable both for protected objects with or protected objects without hot spots High set overcurrent protection operating in stantaneously or with de...

Страница 3: ...ontact functions This contact information is used e g for the blocking of co operating protective re layslocatedupstreams forconnectiontoannun ciator units etc The motor protection relay contains one...

Страница 4: ...I START I RESTART INHIBIT RESTART INHIBIT RELAY RESET i a t EXTERNAL TRIP I x t 2 s s 25 26 27 1 2 3 4 5 6 7 8 9 1 A 5 A 1 A 5 A 1 A 5 A 1 A 5 A SERIAL PORT SPA ZC_ Rx Tx 61 62 U aux SGR1 7 SGR1 6 SG...

Страница 5: ...and output relay module SPTU 240 R2 or SPTU 48 R2 with a normally open trip contact SPTU 240 R3 or SPTU 48 R3 with a normally closed trip contact U3 Input module SPTE 4E3 SPA ZC Bus connection module...

Страница 6: ...odule The communication mode selector switches on the bus connection module are set in position SPA The three phase currents are connected to ter minals 1 2 4 5 and 7 8 when the rated current of the s...

Страница 7: ...SGR2 7 SGR1 8 SGR2 3 STALL RESTART INH SGB 3 SGR2 2 1 SG4 3 SG4 2 6x Fig 4 Control signals between the modules of the motor protection relay SPAM 150 C the measuring relay module The functions of thed...

Страница 8: ...50Hz 60Hz A The operation indicator TRIP is lit when one of the protection stages operates When the protection stage resets the red indicator remains alight Indication Explanation 1 a The thermal lev...

Страница 9: ...x 80 265 V ac dc 18 80 V dc Unstabilized logics voltage Operation amplifier voltage Output relay coil voltage Fig 5 Voltage levels of the power supply module A green LED indicator Uaux on the system f...

Страница 10: ...A 1 A 1 A 0 25 A 0 15 A Breaking capacity for ac 5 A 5 A Signalling contacts Terminals 70 71 72 68 69 77 78 80 81 Rated voltage 250 V dc ac Rated current 5 A Make and carry for 0 5 s 10 A Make and ca...

Страница 11: ...n unit Setting range for I0 1 0 100 In Operate time t0 0 05 30 s Attenuation of the third harmonic typ 20 dB Phase unbalance unit Basic sensitivity I stabilized to phase current levels below I 10 40 x...

Страница 12: ...st IEC 60255 22 2 and IEC 61000 4 2 contact discharge 6 kV air discharge 8 kV Fast transient disturbance test IEC 60255 22 4 and IEC 61000 4 4 power supply 4 kV I O ports 2 kV Mechanical tests tested...

Страница 13: ...information about checking overhaul and re calibration of the relay Note Numerical protection relays contain electronic circuitswhichareliabletoseriousdamagedueto electrostatic discharge Before removi...

Страница 14: ...over is also IP 54 A terminal strip and two multipole connectors are mounted on the back of the relay case to facilitate all input and output connections To each heavy duty terminal i e the measuring...

Страница 15: ...indicator Internal Relay Fault Display 1 3 digits Reset Step push button Programming push button Trip indicator Module type designation Fastening screw Indicators for measured quantities Indicators fo...

Страница 16: ...SGB SGR 4 Settings 4 Setting mode 4 Example 1 Setting of relay operation values 7 Example 2 Setting of relay switchgroups 9 Recorded information 11 Trip test function 12 Example 3 Forced activation of...

Страница 17: ...ion are accessible in the main menu i e present meas ured values present setting values and recorded parameter values The data to be shown in the main menu are sequentially called up for display by me...

Страница 18: ...cation bus 2 By an external control signal BS1 BS2 or RRES BS3 3 Via the push buttons of the relay module see submenu 4 of register A Setting mode Generally when a large number of settings is to be al...

Страница 19: ...willshowthreedashes toindicatethenon tripping mode The serial communication is operativeandallmainandsubmenuesareacces sible In the non tripping mode unnecessary trippings are avoided and the settings...

Страница 20: ...se L2 Event n 2 value of phase L2 Latest memorized event n value of phase L2 2 1 2 Event n 1 value of phase L3 Event n 2 value of phase L3 Latest memorized event n value of phase L3 3 1 2 Main setting...

Отзывы: