Note!
The event codes E52-E54 are generated by the
data communication unit (SACO 100M, SRIO
500M, SRIO 1000M, etc.)
Code
Event
Weight factor
Default value
of the factor
E9
Starting of stage I
0
>
1
1
E10
Resetting of starting of stage I
0
>
2
0
E11
Operation of stage I
0
>
4
1
E12
Resetting of operation of stage I
0
>
8
0
E13
Starting of I
0
>> stage
16
1
E14
Resetting of starting of stage I
0
>>
32
0
E15
Operation of stage I
0
>>
64
1
E16
Resetting of operation of stage I
0
>>
128
0
Default checksum for mask V156
85
E17
Output signal TS1 activated
1
0
E18
Output signal TS1 reset
2
0
E19
Output signal SS1 activated
4
0
E20
Output signal SS1 reset
8
0
E21
Output signal SS2 activated
16
0
E22
Output signal SS2 reset
32
0
E23
Output signal SS3 activated
64
0
E24
Output signal SS3 reset
128
0
E25
Output signal TS2 activated
256
1
E26
Output signal TS2 reset
512
1
Default checksum for mask V157
768
E50
Restarting
*
-
E51
Overflow of event register
*
-
E52
Temporary interruption in data communication
*
-
E53
No response from the module over the data
communication
*
-
E54
The module responds again over the data
communication
*
-
0
not included in the event reporting
1
included in the event reporting
*
no code number
-
cannot be programmed