13
Switch
Function
Factory
Checksum
number
setting
value
SGR3/1 When SGR3/1 = 1, the start signal of the I> stage
is routed to TS1
0
1
SGR3/2 When SGR3/2 = 1, the trip signal of the I> stage
is routed to TS1
0
2
SGR3/3 When SGR3/3 = 1, the start signal of the I>> stage
is routed to TS1
0
4
SGR3/4 When SGR3/4 = 1, the trip signal of the I>> stage
is routed to TS1
0
8
SGR3/5 When SGR3/5 = 1, the start signal of the I
0
> stage
is routed to TS1
0
16
SGR3/6 When SGR3/6 = 1, the trip signal of the I
0
> stage
is routed to TS1
0
32
SGR3/7 When SGR3/7 = 1, the start signal of the I
0
>> stage
is routed to TS1
0
64
SGR3/8 When SGR3/8 = 1, the trip signal of the I
0
>> stage
is routed to TS1
0
128
Checksum for the factory settings of switchgroup SGR3
0
displayed at the present time is indicated by a
LED indicator on the front panel.
Indicator
Measured data
I
L1
Line current on phase L1 as a multiple of the rated current I
n
of the used
energizing input (0…63 x I
n
).
I
L2
Line current on phase L2 as a multiple of the rated current I
n
of the used
energizing input (0…63 x I
n
).
I
L3
Line current on phase L3 as a multiple of the rated current I
n
of the used
energizing input (0…63 x I
n
).
I
0
Residual current as a multiple of the rated current I
n
of the used energizing
input (0…21 x I
n
).
Measured data
The measured current values are shown by the
three right-most digits of the display. The value