9
I/O module SPTR 6B11 has a fixed 40 ms delay
for the control of output relays B and C. This
delay is added to the normal operation delay.
When output B is used as a second trip output
the fixed 40 ms delay is by-passed by means of
switch SGR/7.
The input signals and output signals of the I/O
module are permanently wired to the card loca-
tions of the feeder terminal. Since the output
signals are individually wired from each card
location to the I/O module, the modules have
to be plugged into the relay case as shown in the
Fig. on the front page to secure that the connec-
tion diagram for the relay assembly corresponds
to the physical function of the relay.
Fig. 4. Block diagram for I/O module SPTR 6B11.
SS1/U1
Overcurrent and earth-fault relay module; I>, I>>, I
0
>, and I
0
>> start signals
SS2/U1
Overcurrent and earth-fault relay module; I>, I>>, I
0
>, and I
0
>> operate signals
TS1/U1
Overcurrent and earth-fault relay module; I>, I>>, I
0
>, and I
0
>> start signals or operate
signal, delayed operate signal; I>, I>>, I
0
>,or I
0
>>
TS2/U1
Overcurrent and earth-fault relay module; I>, I>>, I
0
>, and I
0
>> operate signals
SS1/U2
Start signal of earth-fault module, stage I
ϕ
>
TS1/U2
Operate signal of earth-fault module, stage I
ϕ
>
TS2/U2
Operate signal of earth-fault module, stage I
ϕ
>>
ARDUE
"Auto-reclosure due" signal from control module
IRF
Self-supervision
ENA
Enable signal for output signals
A (TRIP)
Operate output 1 of protection relay modules; I>, I>>, I
0
>, I
0
>>, I
ϕ
> and I
ϕ
>> operating,
I>, I>>, I
0
> and I
0
>> starting, delayed operation signal from I>, I>>, I
0
> or I
0
>>
B (SIGNAL1)
Signal on final operation of overcurrent and earth-fault relay module or operation output
2 of protection relay modules; I>, I>>, I
0
>, I
0
>>, I
ϕ
> and I
ϕ
>> operating, I>, I>>, I
0
>
and I
0
>> starting, delayed operation signal from I>, I>>, I
0
> or I
0
>>
C (SIGNAL 2) Signal on final operation of earth-fault module or general signal output, stages I>, I>>, I
0
>,
I
0
>>, I
ϕ
>, I
ϕ
>>
D (SIGNAL 3) Output relay for signals SS1 and SS2 of the overcurrent and earth-fault relay module
E (SIGNAL 4)
Output relay for the start signal of the earth-fault module, stage I
ϕ
>
F (IRF)
Self-supervision alarm output
BACTRL
Selection of Isin
ϕ
/Icos
ϕ
operation for earth-fault module using an external control voltage
BS1
Blocking signal 1 for operation of protection relay modules
BS2
Blocking signal 2 for operation of protection relay modules
+
-
-
+
+
F
E
D
C
B
A
SGR/1
SGR/8
SGR/7
SGR/3
40
ms
40
ms
1
1
1
1
1
SGR/2
1
BS1
BACTRL
BS2
IRF
SS1/U1
SS2/U1
SS1/U2
ARDUE
TS1/U2
TS2/U2
TS1/U1
TS2/U1
X1/12
X1/11
X2/12
X2/11
X2/10
X1/8
X1/9
X1/10
X2/7
X2/8
X2/9
X2/4
X2/5
X2/6
X2/1
X2/2
X2/3
X1/6
X1/7
X1/3
X1/4
TRIP
SIGNAL1
SIGNAL2
SIGNAL3
SIGNAL
4
IRF
ENA
1
1
BS1
BS2
BACTRL
SPTR 6B11