13
Example 2:
To configure five objects (indicators 101, 109
and 103 for disconnectors, indicator 102 for a
circuit breaker and indicator 108 for an earth
switch), the following commands are required:
>99WS198:0:XX
; Enter into setting mode
>99WS100:0:XX
; Enter into mode for free configuration
>99WS101:1,1,1,20,0:XX ; Disconnector 1: vertical red LEDs indicate closed status
for input channel 1.
Control outputs OPEN1 and CLOSE1
>99WS109:1,1,2,22,0:XX ; Disconnector 2: vertical red LEDs indicate closed status
for input channel 2.
Control outputs OPEN2 and CLOSE2
>99WS102:1,1,3,24,1:XX ; Circuit breaker:
vertical red LEDs indicate closed status
for input channel 3.
Controloutputs OPEN3 and CLOSE3
>99WS103:1,1,4,0,0:XX
; Disconnector 3: vertical red LEDs indicate closed status
for input channel 4.
No control
>99WS108:1,0,5,0,0:XX
; Earthing switch: horizontal red LEDs indicate closed status
for input channel 5.
No control
>99WV151:1:XX
; Store the set parameters
After this the interlocking program has to be
written before it is possible to open or close the
circuit breaker and the disconnectors. See Chap-
ter "Interlocking".
The selected configuration can be read indicator
by indicator or all together with one single
instruction.
Example 3:
Reading the configurations of indicators 101…
116 by using one single instruction.
>99RS101/116:XX
This instruction will give the setting values of
each indicator (101 to 116 ), including those not
configured into the system. The parameter val-
ues of the indicators not in use are zero.
913B
Fig. 7. Object configuration set in example 2.