12
Output relay matrix
switchgroups SGR1,
SGR2 and SGR3
SGR1
The switches of switchgroup SGR1 are used to select the protective stages to be
brought to the starting signal output SS1 and the tripping signal output TS2.
SGR2
The switches of switchgroup SGR2 are used for configuring the tripping signals of
the different protective stages. There are two outputs, SS2 and SS3, to which the
signals can be linked.
SGR3
The switches of switchgroup SGR3 are used for configurating the starting and trip-
ping signals to the starting or auxiliary tripping output TS1.
Note!
If the circuit breaker failure protection has been selected in with switch SGF1/4, it
will also utilize the TS1 output.
Switch
Function
Factory Checksum
setting
value
SGR1/1
When SGR1/1 = 1, the starting signal of stage I>
is linked to SS1
1
1
SGR1/2
When SGR1/2 = 1, the tripping signal of stage I>
is linked to TS2
1
2
SGR1/3
When SGR1/3 = 1, the starting signal of stage I>> is
linked to SS1
0
4
SGR1/4
When SGR1/4 = 1, the tripping signal of stage I>> is
linked to TS2
1
8
SGR1/5
When SGR1/5 = 1, the starting signal of stage I
0
> is
linked to SS1
0
16
SGR1/6
When SGR1/6 = 1, the tripping signal of stage I
0
> is
linked to TS2
1
32
SGR1/7
When SGR1/7 = 1, the staring signal of stage I
0
>> is
linked to SS1
0
64
SGR1/8
When SGR1/8 = 1, the tripping signal of stage I
0
>> is
linked to TS2
1
128
Checksum for factory setting of SGR1
171
SGR2/1
When SGR2/1 = 1, the tripping signal from stage I> is
linked to SS2
1
1
SGR2/2
When SGR2/2 = 1, the tripping signal from stage I> is
linked to SS3
0
2
SGR2/3
When SGR2/3 = 1, the tripping signal from stage I>> is
linked to SS2
1
4
SGR2/4
When SGR2/4 = 1, the tripping signal from stage I>> is
linked to SS3
0
8
SGR2/5
When SGR2/5 = 1, the tripping signal from stage I
0
> is
linked to SS2
0
16
SGR2/6
When SGR2/6 = 1, the tripping signal from stage I
0
> is
linked to SS3
1
32
SGR2/7
When SGR2/7 = 1, the tripping signal from stage I
0
>> is
linked to SS2
0
64
SGR2/8
When SGR2/8 = 1, the tripping signal from stage I
0
>> is
linked to SS3
1
128
Checksum for factory setting of SGR2
165