11
Example 2: Indicator 109 (S109) indicates the
status read via input channel 2. Output 20 is
used for opening the object which means that
output 21 must be used for closing the same
object. The object is a circuit breaker and the
closed status is indicated by vertical red LEDs.
The command has the formula:
>99 WS 109:1,1,2,20,1:XX
Type of object
0 = not circuit breaker
1 = circuit breaker
Output code
0 = object is not controlled
20 = code of OPEN output
21 = code of CLOSE output
Note! Either 20 or 21 can be used if the object is
to be controlled.
Input channel number
Channels 1…3
Defines the vertical/horizontal position of open/closed indication
0 = vertical LEDs indicate open status (horizontal LEDs indicate
closed status)
1 = vertical LEDs indicate closed status (horizontal LEDs indicate
open status)
Defines the use of object indicator
0 = not used
1 = used
Number of object indicator
Write Setting
Data communication address
Default value is 99
Syntax rules for programming the configura-
tion for SPTO 1D2:
1. The programming has to be done in the
program mode.
2. Maximum three objects can be configured
(three settings in the range of S101…S116).
3. Only input channel numbers 1…3 are ac-
cepted. Each number can be used only once.
4. If an object indicator is not used, no other
values need to be given.
5. Output code 20 or 21 can be given only once.
If the output code is 0, the definition of the
object (CB/other object) need not be given.
6. Only one object can be defined to be a circuit
breaker.