5
Front panel
IRF
2
5
(
n =
/
A
)
5
1
I
I
n =
/
A
( )
5
1
o
I
I
f
n =
50
60 Hz
RS 615
Ser.No.
1923
SPTO 1D2
O I
U
aux
30 ... 80 V
_
80 ... 265 V
_
R
L
SG1
1
2
0 1
I
STEP
SPAC 3__ C
I
I
L1
L2
L3
[kA]
[kA]
[kA]
O
I
TEST
INTERLOCK
[MW]
[Mvar]
[GWh, MWh, kWh]
P
Q
E
RS 232
GAS PRESSURE
MOTOR VOLTAGE
Operation indicators;
output test and interlocked
operation
Indicators for input
channels 4…9
The pocket for channel
legend text film SYKU 997
Remote/Local key switch
Indicators for remote and
local mode
Indicator for auxiliary power
supply
Voltage range of power
supply and binary inputs
Type designation and
rated values of the relay
package
Simplified device
symbol
Display for measured
values
Self-supervision
alarm indicator
Display step button
Indicators for
measured values
Switchgroup SG1
RS 232 interface
Type designation
of the module
Status indication matrix
The pocket for configuration
plate SYKK _
Select, close
and open
buttons
Fig. 2. Front panel of the control module SPTO 1D2 without the configuration plate SYKK __ and
the channel legend text foil SYKU 997.
The front panel has 16 LED indicators for local
status indication. The indicators are arranged as
a 4 x 4 matrix. Three of these indicators can be
used simultaneously in the control module SPTO
1D2. The combination of indicators used is
freely programmable by the user, see chapter
"Configuration".
In front of the indicators there is a pocket for a
separate plastic configuration plate type SYKK_.
The bottom of the pocket is open. By changing
the configuration plate and programming a new
indicator combination different kinds of bays
can be described.
The circuit breakers and disconnectors of the
bay are shown on the configuration plate. The
configuration plate has a transparent window in
front of the indicators that are in use. The
unused indicators are hidden.
One object indicator is composed of four LEDs,
two vertical and two horizontal. Two of the
LEDs are red and two are green. The red LEDs
are vertical and the green LEDs horizontal in
columns 1 and 3, see Fig. 6. In the columns 2
and 4 the green LEDs are vertical and the red
LEDs horizontal. Due to this system both col-
ours can be used to indicate either open or closed
status.
Fig. 3. Example of plastic configuration plate
SYKK _. The size of the plate is 72 x 106.5 mm.
912B
Object status
indicators