Electrical connections
32 - EN
Sensyflow FMT500-IG
CI/FMT500-IG-EN
5.1.2 PROFIBUS
DPV1
communication
with DP M12 connector socket
The version with PROFIBUS DP M12 connector socket allows
disconnection of the device from the bus without interrupting
PROFIBUS DP operation. Instead of the center cable gland an
assembled and wired DP M12 connector socket is supplied.
For connection to the PROFIBUS DP line you need 1 T-plug, cable
socket and cable plug (see accessories).
Type of protection of the plug-in connections: IP 66.
Only available for non-Ex devices in integral mount design.
Please refer to Data Sheet 10/63-6.40 for other versions of T-plugs and
appropriate DP connector plugs.
Pin assignment of the device
Pin Signal
Description
1
VP
+ 5 V
2
RxD/TxD-N
Receive / transmit data
line
A
(green
wire)
3
DGND
Data transmission potential
4
RxD/TxD-P
Receive / transmit data
line
B
(red
wire)
5
Shield
Shield / protective earth
Thread Shield
Shield / protective earth