L2275
Emax UL
80/132
Doc. N°
Mod.
RH0109002
Apparatus
Scale
Page N°
(*) Parameters set with these values only for PR113 sold as a loose piece.
“EDIT”:
&
Everything allowed in READ mode
&
Configuration of the unit
&
Programming of the parameters relative to the protections
&
TEST Functions of the unit
To access to the “EDIT” mode, it is necessary to press the
↵
key on of a page with fields which can be edited. A password will therefore be required
to enable passing into the editing mode.
15.2.12 Default settings
The PR113/P-A is supplied by ABB SACE with the following predefined parameters:
#
Protection
On/Off
Threshold
Time
Curves
T.M.
Z S
Trip
1
L
--
1 In
144 s
I
2
t
Off
--
--
2
S
Off
6 In
min
K
--
Off: 0.04s --
3
D
Off
6 In
0.2s-0.2s
Off: 0.13s
4
I
On
4 In
--
--
--
--
--
5
G
Off
0.2 In
0.4 s
K
--
Off: 0.04s On
6
U
Off
50 %
5 s
Off
7
O T
--
See par.15.2.6.7
Off
8
K
Off
9
UV
Off
0.9 Un
5 s
Off
10
OV
Off
1.05 Un
5 s
11
RV
Off
0.15 Un
15 s
12
RP
Off
- 0.1 Pn
10 s
13
Iinst
On
E1 (*)
--
14
Language
--
Engl
15
Net Frequency
--
60 Hz
16
PR020/K
Off
17
PR020/K relays
--- (Off)
18
Neutral sel.
--
50 %
19
Toroid Selec.
--
Int.
20
CB
--
E1B-A800 (*)
21
CS In
--
250 A (*)
22
Ext. tor. In
---- (Off)
100 A
23
Vs Un
--
380/
√
3 V
24
Startup Thresholds
Off
--
0.10 s
25
S startup (threshold)
---- (Off)
---- In
26
D startup (threshold)
---- (Off)
---- In
27
I startup (threshold)
---- (Off)
---- In
28
G startup (threshold)
---- (Off)
---- In
29
Password
--
0001
30
Store Meas. T.
--
60 min.
31
Warning Current Thre.
-- (Off)
--
32
PR113 Relay 1
PL
33
PR113 Relay 2
Off