GlobalBaseSel
: Selects the global base value group used by the function to define
(
IBase
), (
UBase
) and (
SBase
).
14.13.6
Operation principle
The input signal must be connected to a range output of a measuring function block
(CVMMXN, CMMXU, VMMXU, VNMMXU, CMSQI, VMSQ or MVGGIO). The
function block converts the input integer value to five binary output signals according
to
.
Table 395:
Input integer value converted to binary output signals
Measured supervised
value is:
below low-low
limit
between low‐
low and low
limit
between low
and high limit
between high-
high and high
limit
above high-
high limit
Output:
LOWLOW
High
LOW
High
NORMAL
High
HIGH
High
HIGHHIGH
High
14.14
Station battery supervision SPVNZBAT
14.14.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Station battery supervision function
SPVNZBAT
U<>
-
14.14.2
Function block
GUID-2D3C21EA-75E9-4E44-AA0F-4DEA7599182A V1 EN
Figure 211:
Function block
14.14.3
Functionality
The station battery supervision function SPVNZBAT is used for monitoring battery
terminal voltage.
1MRK 504 135-UEN A
Section 14
Monitoring
489
Technical manual
Содержание ret650
Страница 1: ...Relion 650 series Transformer protection RET650 Technical manual ...
Страница 2: ......
Страница 40: ...34 ...
Страница 62: ...56 ...
Страница 84: ...78 ...
Страница 208: ...202 ...
Страница 353: ...Table 236 Gray code conversion IEC06000523 V1 EN 1MRK 504 135 UEN A Section 12 Control 347 Technical manual ...
Страница 376: ...370 ...
Страница 414: ...408 ...
Страница 530: ...524 ...
Страница 562: ...556 ...
Страница 620: ...614 ...
Страница 668: ...662 ...
Страница 669: ...663 ...