Table 18. Electromagnetic compatibility tests, continued
Description
Type test value
Reference
Voltage dips and interruptions on AC power
supply
Dips:
40% 10/12 cycles at 50/60 Hz
70% 25/30 cycles at 50/60 Hz
Interruptions:
0–50 ms: No restart
0...∞ s: Correct behaviour at power down
IEC 60255–11
IEC 61000–4–11
Electromagnetic emission tests
EN 55011, class A
IEC 60255-25
ANSI C63.4, FCC
• Conducted, RF-emission (mains terminal)
0.15...0.50 MHz
< 79 dB(µV) quasi peak
< 66 dB(µV) average
0.5...30 MHz
< 73 dB(µV) quasi peak
< 60 dB(µV) average
• Radiated RF-emission, IEC
30...230 MHz
< 40 dB(µV/m) quasi peak, measured at 10 m
distance
230...1000 MHz
< 47 dB(µV/m) quasi peak, measured at 10 m
distance
Table 19. Insulation tests
Description
Type test value
Reference
Dielectric tests:
IEC 60255-5
ANSI C37.90-2005
• Test voltage
2 kV, 50 Hz, 1 min
1 kV, 50 Hz, 1 min, communication
Impulse voltage test:
IEC 60255-5
ANSI C37.90-2005
• Test voltage
5 kV, unipolar impulses, waveform 1.2/50 μs,
source energy 0.5 J
1 kV, unipolar impulses, waveform 1.2/50 μs,
source energy 0.5 J, communication
Insulation resistance measurements
IEC 60255-5
ANSI C37.90-2005
• Isolation resistance
>100 MΏ, 500 V DC
Protective bonding resistance
IEC 60255-27
• Resistance
<0.1 Ώ (60 s)
Transformer protection RET650
1MRK 504 137-BEN B
Product version: 1.3
36