Table 31. Instantaneous residual overcurrent protection EFPIOC
Function
Range or value
Accuracy
Operate current
(1-2500)% of lBase
±
1.0% of I
r
at I
£
I
r
±
1.0% of I at I > I
r
Reset ratio
> 95%
-
Operate time
20 ms typically at 0 to 2 x I
set
-
Reset time
30 ms typically at 2 to 0 x I
set
-
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Operate time
10 ms typically at 0 to 5x I
set
-
Reset time
40 ms typically at 5 to 0x I
set
-
Critical impulse time
2 ms typically at 0 to 5 x I
set
-
Dynamic overreach
< 5% at
t
= 100 ms
-
Transformer protection RET650
1MRK 504 137-BEN B
Product version: 1.3