Section 2
1MAC254287-MB B
DNP3 data mappings
34
REM615 ANSI
Point List Manual
Table 90:
FLO:Fault location (DRFLO1)
AI
161
Class 2 and 0
Yes
Last Fault: Zero Sequence Voltage
Magnitude
1
LD0.FLTMSTA1.VZroSeq.mag.f
AI
162
Class 2 and 0
Yes
Last Fault: Positive Sequence
Voltage Magnitude
1
LD0.FLTMSTA1.VPsSeq.mag.f
AI
163
Class 2 and 0
Yes
Last Fault: Negative Sequence
Voltage Magnitude
1
LD0.FLTMSTA1.VNgSeq.mag.f
AI
164
Class 2 and 0
Yes
Phase A voltage (b)
100
LD0.FLTMSTA1.VoltsAb.mag.f
AI
165
Class 2 and 0
Yes
Phase B voltage (b)
100
LD0.FLTMSTA1.VoltsBb.mag.f
AI
166
Class 2 and 0
Yes
Phase C voltage (b)
100
LD0.FLTMSTA1.VoltsCb.mag.f
AI
167
Class 2 and 0
Yes
Phase A to phase B voltage (b)
100
LD0.FLTMSTA1.VoltsABb.mag.f
AI
168
Class 2 and 0
Yes
Phase B to phase C voltage (b)
100
LD0.FLTMSTA1.VoltsBCb.mag.f
AI
169
Class 2 and 0
Yes
Phase C to phase A voltage (b)
100
LD0.FLTMSTA1.VoltsCAb.mag.f
AI
170
Class 2 and 0
Yes
Residual voltage (b)
100
LD0.FLTMSTA1.VoltsNb.mag.f
AI
171
Class 2 and 0
Yes
Zero sequence voltage (b)
100
LD0.FLTMSTA1.VZroSeqb.mag.f
AI
172
Class 2 and 0
Yes
Positive sequence voltage (b)
100
LD0.FLTMSTA1.VPsSeqb.mag.f
AI
173
Class 2 and 0
Yes
Negative sequence voltage (b)
100
LD0.FLTMSTA1.VNgSeqb.mag.f
AI
175
Class 2 and 0
Yes
Last Fault: I2/I1 Ratio Fault
1
LD0.FLTMSTA1.PDNS1MxRat.mag.f
AI
176
Class 2 and 0
Yes
Last Fault: Frequency At The Time
The Fault Is Cleared
1
LD0.FLTMSTA1.Hz.mag.f
AI
177
Class 2 and 0
Yes
Last Fault: Frequency Gradient At
The Time The Fault Is Cleared
1
LD0.FLTMSTA1.HzS.mag.f
AI
178
Class 2 and 0
Yes
Last Fault: Conductance Yo
1
LD0.FLTMSTA1.CondN.mag.f
AI
179
Class 2 and 0
Yes
Last Fault: Susceptance Yo
1
LD0.FLTMSTA1.SusN.mag.f
AI
403
Class 2 and 0
Yes
Distance to fault measured in pu
1
LD0.FLTMSTA1.FltDisKm.mag.f
AI
404
Class 2 and 0
Yes
Active Setting at time of Fault
1
LD0.FLTMSTA1.ActSG.stVal
AI
405
Class 2 and 0
Yes
Last Fault: Max Temperature
1
LD0.FLTMSTA1.MaxTmpRl.mag.f
DNP
Object
Type
No
Event
Point
Index
DNP Class
Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
DNP
Object
Type
No
Event
Point
Index
DNP Class
Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI
Yes
541
Class 0
Yes
FLO Relay Trip
LD0.DRFLO1.Tr.general
AI
225
Class 2 and 0
Yes
FLO Distance to fault measured in
Km/Miles
1
LD0.DRFLO1.FltDisKm.mag.f
Содержание REM615 ANSI
Страница 1: ...Relion 615 Series Motor Protection and Control REM615 ANSI DNP3 Point List Manual...
Страница 2: ......
Страница 8: ...Section 1MAC254287 MB B 2 REM615 ANSI Point List Manual...
Страница 50: ...Section 3 1MAC254287 MB B DNP3 protocol implementation 44 REM615 ANSI Point List Manual...
Страница 52: ...Section 4 1MAC254287 MB B Glossary 46 REM615 ANSI Point List Manual Val Value...
Страница 53: ......