Section 2
1MAC254287-MB B
DNP3 data mappings
14
REM615 ANSI
Point List Manual
Table 24:
81:Frequency protection-instance 1 (FRPFRC1)
Table 25:
46M-1:Negative-sequence overcurrent protection for motors-instance 1 (MNSPTOC1)
Table 26:
46M-2:Negative-sequence overcurrent protection for motors-instance 2 (MNSPTOC2)
Table 27:
37M-1:Loss of load supervision-instance 1 (LOFLPTUC1)
Table 28:
37M-2:Loss of load supervision -instance 2 (LOFLPTUC2)
Table 29:
51LR:Motor load jam protection (JAMPTOC1)
Table 30:
66/51LRS:Motor start-up supervision (STTPMSS1)
DNP
Object
Type
No
Event
Point
Index
DNP Class
Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI
352
Class 1 and 0
Yes
81 Frequency Gradient Trip (Operate)
LD0.FRPFRC1.Op.general
AI
Yes
205
Class 0
Yes
81 Ratio Of Pickup (Start) Time / Trip
(Operate) Time Frequency Gradient
Instance 1
100
LD0.FRPFRC1.StrDur.mag.f
DNP
Object
Type
No
Event
Point
Index
DNP Class
Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI
328
Class 1 and 0
Yes
46M-1 Negative Sequence Overcurrent
Protection For Motors 1
LD0.MNSPTOC1.Op.general
DNP
Object
Type
No
Event
Point
Index
DNP Class
Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI
329
Class 1 and 0
Yes
46M-2 Negative Sequence Overcurrent
Protection For Motors 2
LD0.MNSPTOC2.Op.general
DNP
Object
Type
No
Event
Point
Index
DNP Class
Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI
330
Class 1 and 0
Yes
37M-1 Loss Of Load Supervision 1
LD0.LOFLPTUC1.Op.general
DNP
Object
Type
No
Event
Point
Index
DNP Class
Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI
331
Class 1 and 0
Yes
37M-2 Loss Of Load Supervision 2
LD0.LOFLPTUC2.Op.general
DNP
Object
Type
No
Event
Point
Index
DNP Class
Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI
320
Class 1 and 0
Yes
51LR Motor Jam Trip (Operate)
LD0.JAMPTOC1.Op.general
BI
321
Class 1 and 0
Yes
51LR Motor Jam Phase A Trip (Operate)
LD0.JAMPTOC1.Op.phsA
BI
322
Class 1 and 0
Yes
51LR Motor Jam Phase B Trip (Operate)
LD0.JAMPTOC1.Op.phsB
BI
323
Class 1 and 0
Yes
51LR Motor Jam Phase C Trip (Operate)
LD0.JAMPTOC1.Op.phsC
DNP
Object
Type
No
Event
Point
Index
DNP Class
Enabled Description
Scale
Factor
IEC61850 Data Attribute Name
BI
324
Class 1 and 0
Yes
66/51LRS Trip (Operate)/Trip Signal For
Stalling Protection
LD0.STTPMSS1.Op.general
Содержание REM615 ANSI
Страница 1: ...Relion 615 Series Motor Protection and Control REM615 ANSI DNP3 Point List Manual...
Страница 2: ......
Страница 8: ...Section 1MAC254287 MB B 2 REM615 ANSI Point List Manual...
Страница 50: ...Section 3 1MAC254287 MB B DNP3 protocol implementation 44 REM615 ANSI Point List Manual...
Страница 52: ...Section 4 1MAC254287 MB B Glossary 46 REM615 ANSI Point List Manual Val Value...
Страница 53: ......