2.3.1.43
LD0.SEQRFUF1 Fuse failure protection
Table 46:
LD0.SEQRFUF1 Fuse failure protection
IEC 61850 name
SA name
Description
Values
LD0.SEQRFUF1
.Str.general
FUSEF_U
General start
1=Start
.Str3Ph.general
FUSEF_3PH
Three-phase start
1=Start
2.3.1.44
LD0.SPCGGIO2 Multipurpose binary outputs - status (2)
Table 47:
LD0.SPCGGIO2 Multipurpose binary outputs - status (2)
IEC 61850 name
SA name
Description
Values
LD0.SPCGGIO2
.SPCS01.stVal
-
Output 1 state
0/1=Off/On
.SPCS02.stVal
-
Output 2 state
0/1=Off/On
.SPCS03.stVal
-
Output 3 state
0/1=Off/On
.SPCS04.stVal
-
Output 4 state
0/1=Off/On
.SPCS05.stVal
-
Output 5 state
0/1=Off/On
.SPCS06.stVal
-
Output 6 state
0/1=Off/On
.SPCS07.stVal
-
Output 7 state
0/1=Off/On
.SPCS08.stVal
-
Output 8 state
0/1=Off/On
.SPCS09.stVal
-
Output 9 state
0/1=Off/On
.SPCS10.stVal
-
Output 10 state
0/1=Off/On
.SPCS11.stVal
-
Output 11 state
0/1=Off/On
.SPCS12.stVal
-
Output 12 state
0/1=Off/On
.SPCS13.stVal
-
Output 13 state
0/1=Off/On
.SPCS14.stVal
-
Output 14 state
0/1=Off/On
.SPCS15.stVal
-
Output 15 state
0/1=Off/On
.SPCS16.stVal
-
Output 16 state
0/1=Off/On
2.3.1.45
LD0.SSCBR1 Circuit-breaker condition monitoring
Table 48:
LD0.SSCBR1 Circuit-breaker condition monitoring
IEC 61850 name
SA name
Description
Values
.APwrAlm.stVal
IPOW_ALM
Iyt alarm
1=Alarm
.APwrLO.stVal
IPOW_LO
Iyt lockout
1=Lockout
.CBLifAlm.stVal
CB_LIFE_ALM
CB lifetime alarm
1=Alarm
.ClsAlm.stVal
TRV_T_CL_ALM
Cls travel time alarm
1=Alarm
.LonTmAlm.stVal
MON_ALM
CB inactive alarm
1=Alarm
.OpnAlm.stVal
TRV_T_OP_ALM
Cls travel time alarm
1=Alarm
Table continues on next page
Section 2
1MRS756880 C
DNP3 data mappings
24
REM615
Point List Manual