2.3.1.3
LD0.ARCSARC3 Fault arc protection stage 3
Table 6:
LD0.ARCSARC3 Fault arc protection stage 3
IEC 61850 name
SA name
Description
Values
LD0.ARCSARC31
.FADet.stVal
ARC_FLT_DET
Arc detected
1=Detected
LD0.ARCPTRC31
.Op.general
OPERATE
Operate
1=Operate
2.3.1.4
CTRL.Cxxxxx1 Circuit breaker (1) CB object and failure protection
Table 7:
CTRL.Cxxxxx1 Circuit breaker (1) CB object and failure protection
IEC 61850 name
SA name
Description
Values
CTRL.CBCILO1
.EnaCls.stVal
ENA_CLOSE
Close enabled
1=Enabled
.EnaOpn.stVal
ENA_OPEN
Open enabled
1=Enabled
.ItlByPss.stVal
ITL_BYPASS
Interlocking bypass
1=Bypassed
CTRL.CBCSWI1
.Pos.stSeld
SELECTED
CB selected
1=Selected
CTRL.CBXCBR1
.BlkCls.stVal
BLK_CLOSE
Close blocked
1=Blocked
.BlkOpn.stVal
BLK_OPEN
Open blocked
1=Blocked
CTRL.CCBRBRF1
.OpEx.general
TRBU
Failure ext.trip
1=Failure
.OpIn.general
TRRET
Operate, re-trip
1=Operate
.Str.general
CB_FAULT_AL
Start, timer running
1=Start
2.3.1.5
CTRL.Dxxxxx1 Controllable disconnector (1)
Table 8:
CTRL.Dxxxxx1 Controllable disconnector (1)
IEC 61850 name
SA name
Description
Values
CTRL.DCCILO1
.EnaCls.stVal
ENA_CLOSE
Close enabled
1=Enabled
.EnaOpn.stVal
ENA_OPEN
Open enabled
1=Enabled
.ItlByPss.stVal
ITL_BYPASS
Interlocking bypass
1=Bypassed
CTRL.DCCSWI1
.Pos.stSeld
SELECTED
CB selected
1=Selected
CTRL.DCXSWI1
.BlkCls.stVal
BLK_CLOSE
Close blocked
1=Blocked
.BlkOpn.stVal
BLK_OPEN
Open blocked
1=Blocked
Section 2
1MRS756880 C
DNP3 data mappings
14
REM615
Point List Manual