Cyclical period
• Min: 1
• Max: 604800
• Default: 10
• Unit: seconds
Cyclical period is the periodical timer for the cyclical data sending. The maximum of
604800 seconds means one week.
3.6.21
Transmit window
• Min: 1
• Max: 32767
• Default: 12
• Unit: APDU
The value of k shall indicate the maximum number of sequentially numbered I format
APDUs that the DTE may have outstanding (i.e. unacknowledged) at a given time. The
transmitter stops the transmission at k unacknowledged I format APDUs.
3.6.22
Receive window
• Min: 1
• Max: 32767
• Default: 8
• Unit: APDU
The receiver acknowledges at the latest after receiving w I format APDUs
Recommendation: w should not exceed two-thirds of k.
3.6.23
Transmit timeout
• Min: 1000
• Max: 255000
• Default: 15000
• Unit: ms
t1 is the timeout of a sent U-frame or I-frame. t1 starts after a U-frame or I-frame message
is sent. When t1 timer expires and no ACK for that message was received, the connection
termination (active close) will be initiated. The accuracy for t1 is 1 second. The timeout
setting should be set as a multiple of 1000ms.
3.6.24
Receive timeout
• Min: 1000
Содержание Rellon 620 Series
Страница 1: ...Relion 620 series RER620 IEC 60870 5 101 104 Communication Protocol Manual ...
Страница 2: ......
Страница 9: ...1MAC306892 MB C Section RER620 3 Communication Protocol Manual Section 5 Glossary 31 ...
Страница 10: ...Section 1MAC306892 MB C 4 RER620 Communication Protocol Manual ...
Страница 32: ...Section 3 1MAC306892 MB C Vendor specific implementation 26 RER620 Communication Protocol Manual ...
Страница 38: ...Section 5 1MAC306892 MB C Glossary 32 RER620 Communication Protocol Manual ...
Страница 39: ......