1MAC306892-MB C
Section 3
Vendor-specific implementation
RER620
21
Communication Protocol Manual
3.6.14
Event time
• Local
• UTC (default)
The setting selects between the time stamp modes for event reporting.
3.6.15
Overflow mode
• Indication (default)
• Keep newest
The setting defines the handling of the event buffer overflow situation. In the oldest
+indication mode, the protective relay discards the newest events to protect the older ones.
In that mode, the protective relay generates an overflow indication event. The keep newest
mode is added for compatibility for the systems that prefer latest information. In that case,
the oldest events in the buffer are discarded.
3.6.16
OvInd IOA
• Min: 0
• Max: 255/65535/16777215
• Default: 60000
The protective relay generates an overflow indication event with this address if the lost
event is included in any of the interrogation groups. Based on this information, the client
requests for interrogation to get the latest momentary values.
• If OvInd IOA is set to 0, the overflow indication is disabled for the points that are part
of some interrogation groups.
• If
OvInd IOA
is set to the same value as
OvInd NoGI IOA
, only one indication event
is generated regardless whether the point is included in the interrogation group or not.
• The maximum value depends on the IOA length setting.
Select the time format which is supported by the client.
Applicable only if
Overflow mode
is set to "Indication".
Содержание Rellon 620 Series
Страница 1: ...Relion 620 series RER620 IEC 60870 5 101 104 Communication Protocol Manual ...
Страница 2: ......
Страница 9: ...1MAC306892 MB C Section RER620 3 Communication Protocol Manual Section 5 Glossary 31 ...
Страница 10: ...Section 1MAC306892 MB C 4 RER620 Communication Protocol Manual ...
Страница 32: ...Section 3 1MAC306892 MB C Vendor specific implementation 26 RER620 Communication Protocol Manual ...
Страница 38: ...Section 5 1MAC306892 MB C Glossary 32 RER620 Communication Protocol Manual ...
Страница 39: ......