7.5.1
Selecting IED test mode
The test mode can be activated using the LHMI. The Home button is flashing green at
low frequency to indicate that the test mode is activated. By default, the test mode can
only be changed from the LHMI. Activation by remote client is possible, see the
technical manual.
The test mode is useful for simulated testing of functions and outputs without
providing current inputs.
•
Select
Testing and Commissioning/Test mode/IED test
to activate the internal
fault test.
GUID-05CFE41C-A635-4032-9484-3854B3403D70 V1 EN
Figure 97:
Selecting IED test mode
If the test mode is not cancelled, it remains on and the Home button
remains flashing.
7.5.2
Testing and commissioning support on local HMI
The LHMI supports the engineer during the relay’s testing, commissioning and
troubleshooting activities. The information, traditionally accessible through different
paths within the menu structure, is provided in a collectively grouped and visualized
format on the Testing and Commissioning pages found on the top bar menu.
Some of the Testing and Commissioning pages require the relay to be
set in test mode.
1MRS759118 A
Section 7
Commissioning
REX640
117
Operation Manual