![ABB RELION REL650 Скачать руководство пользователя страница 54](http://html1.mh-extra.com/html/abb/relion-rel650/relion-rel650_operation-manual_3413656054.webp)
Table 5:
Warning indications
Warning indication
Additional information
Warning
IEC 61850 Error
IEC 61850 has not
succeeded in some actions
such as reading the
configuration file, startup
etc.
Warning
GOOSE Error
One or more access point is
not able to run GOOSE due
to GOOSE being
deactivated on the access
point, or the access point
being deactivated or failing.
7.2.3
Additional indications
GUID-69561C77-50E8-45E2-B8AC-80116222B5B9 v3
The additional indication messages do not activate internal fault or warning.
The messages are listed in the LHMI menu under the event list. The signal status data is found
under the IED status and in the internal event list.
Table 6:
Additional indications
Warning indication
Additional information
Time Synch Error
Source of the time synchronization is lost or time
system has made a time reset.
Settings Changed
Settings have been changed.
Setting Groups Changed
Setting group has been changed.
7.3
Correction procedures
7.3.1
Creating user accounts and setting and changing passwords
GUID-D3FA85BA-1E36-4F8B-BD71-85C7AC46A0B4 v2
If Central Account Management is disabled in the IED, user account creation, initial password
setting and password changing is done using PCM600.
If Central Account Management is enabled in the IED, user account creation and initial
password setting is done using the SDM600 server. Individual users can then change their
passwords via PCM600 or the LHMI.
For more information, see PCM600 documentation or the Cyber security
deployment guidelines.
7.3.1.1
Changing the password from the LHMI
GUID-5A50512E-ECF6-4957-BE57-E11DE253DAAC v1
The password can only be changed for the active user.
1.
Press
.
2.
Select Change Password and press
to confirm.
Section 7
1MRK 500 125-UEN A
Troubleshooting
48
Operation manual