GUID-4606198B-521D-4804-BBC8-8E041E144026 V1 EN
Figure 53:
Adding a measurand object to an LHMI view
2.
In the
Objects Properties
view, edit the name, unit and the number of decimals.
Unit text
specifies the default text used for the measurement's unit. If
Unit text
is
not empty, the unit in the IED is updated dynamically based on the signal it is
connected to. If the
Unit text
is empty in the Graphical Display Editor, no unit is
shown. The
Scale factor
parameter is not used.
6.1.1.9
Adding a busbar
1.
Add at least two
Busbar Junctions
.
2.
Add links between the
Busbar Junctions
.
Section 6
1MRS240044-IB A
LHMI engineering
90
REF615R
Engineering Manual