Setting up an IED in the offline mode is similar as in the online mode; however,
with the offline mode it is not necessary to type the correct IP address in the
Communication port and IP address
dialog box.
4.
On the order code selection page, select the correct order codes.
5.
Click
Generate
to generate the functions for the selected order code.
A
Function generation complete
dialog box is shown. Click
Close
.
6.
Click
Next
on the
Setup Complete Page
that shows the summary of the IED
type, version, IP address and the selected order number.
7.
Click
Finish
to confirm the configuration and conduct the insertion.
4.6.3
Inserting an IED from the template directory
IED templates can be used for replicating IEDs with same order code in PCM600
projects. Template includes IED application configuration, graphical display
configuration (single-line diagram), communication protocol mappings and
parameters. An IED in the plant structure can be exported as a template (.pcmt file).
The template library can be built from all the exported IED templates.
It is also possible to insert an IED from the template library to create a new IED in the
plant structure. After a template IED has been imported, the
IP address
, the
Caption
in
IED
Object Properties
and the
Technical Key
that corresponds to the physical IED
have to be changed.
A template IED can be inserted only when the bay is selected in the
plant structure.
1.
In the
Plant structure
view, select the bay, right-click, point to
New
and select
Create from template
.
The
Create New Object from Template
dialog box opens.
1MRS240044-IB A
Section 4
Setting up a project
REF615R
41
Engineering Manual