Feeder Protection and Control
REF615
Product version: 2.0
1MRS756379 D
Control functions
Table 57. Autoreclosure (DARREC)
Operation accuracy
±1.0% of the set value or ±20 ms
Table 55. Arc protection (ARCSARC) main settings
Parameter
Function
Value (Range)
Step
Phase start value
(Operating phase current)
ARCSARC
0.50...40.00 x I
n
0.01
Ground start value
(Operating residual current)
ARCSARC
0.05...8.00 x I
n
0.01
Operation mode
ARCSARC
1=Light+current
2=Light only
3=BI controlled
Table 56. Operating characteristics
Parameter
Values (Range)
Operating curve type
(current protection)
1=ANSI Ext. inv.
2=ANSI Very. inv.
3=ANSI Norm. inv.
4=ANSI Mod inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Operating curve type
(voltage protection)
5=ANSI Def. Time
15=IEC Def. Time
17=Inv. Curve A
18=Inv. Curve B
19=Inv. Curve C
20=Programmable
21=Inv. Curve A
22=Inv. Curve B
23=Programmable