ABB
26
Feeder Protection and Control
REF615
Product version: 2.0
1MRS756379 D
Table 28. Non-directional EF protection (EFxPTOC)
Operation
accuracy
Depending on the frequency of the current measured: f
n
±2Hz
EFLPTOC
±1.5% of the set value or ±0.002 x I
n
EFHPTOC
and
EFIPTOC
±1.5% of set value or ±0.002 x I
n
(at currents in the range of 0.1…10 x I
n
)
±5.0% of the set value
(at currents in the range of 10…40 x I
n
)
Start time
1) 2)
Minimum
Typical
Maximum
EFIPTOC:
I
Fault
= 2 x set
Start value
I
Fault
= 10 x set
Start value
16 ms
11 ms
19 ms
12 ms
23 ms
14 ms
EFHPTOC and EFLPTOC:
I
Fault
= 2 x set
Start value
22 ms
24 ms
25 ms
Reset time
< 40 ms
Reset ratio
Typical 0.96
Retardation time
< 30 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
RMS: No suppression DFT: -50dB at f =
n x f
n
, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
1)
Measurement mode
= default (depends on stage), current before fault = 0.0 x In, fn = 50 Hz, earth-fault current
with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
2) Includes the delay of the signal output contact
3) Maximum
Start value
= 2.5 x In,
Start value
multiples in range of 1.5 to 20
Table 29. Non-directional EF protection (EFxPTOC) main settings
Parameter
Function
Value (Range)
Step
Start value
EFLPTOC
0.010...5.000 x I
n
0.005
EFHPTOC
0.10...40.00 x I
n
0.01
EFIPTOC
1.00...40.00 x I
n
0.01
Time multiplier
EFLPTOC
0.05...15.00
0.05
EFHPTOC
0.05...15.00
0.05
Operate delay time
EFLPTOC
40...200000 ms
10
EFHPTOC
40...200000 ms
10
EFIPTOC
20...200000 ms
10
Operating curve type
1)
EFLPTOC
Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10,
11, 12, 13, 14, 15, 17, 18, 19
EFHPTOC
Definite or inverse time
Curve type: 1, 3, 5, 9, 10, 12, 15, 17
EFIPTOC
Definite time
1) For further reference please refer to the Operating characteristics table at the end of the Technical data chapter