18
1MRS 755539
Feeder Protection Relay
Operator’s Manual - ANSI Version
REF 610
3.1.11.1.
Target LED for front communication
• Target off:
Rear communication is currently selected
• Lit target:
Front communication port is currently selected
• Blinking target:
Front communication port is currently selected and the relay is communicating
3.1.12.
How to select the protocol for rear communication
When REF 610 is provided with a communication module for the built-in
communication protocols, it allows you to choose the communication protocol for
rear connection. If REF 610 is equipped with a protocol specific communication
module, no communication protocol selections are allowed. The protocol is then
defined by the communication module. The selected protocol is stored in the non-
volatile memory and will therefore be activated automatically after an interruption
in the auxiliary voltage.
Select the rear communication protocol as follows:
1. Press an arrow button to access the main menu.
2. Use the arrow buttons to select
CONFIGURATION\COMMUNICATION\REAR
PROTOCOL
and press
. The cursor will be at the setting currently in use (e.g.
SPA
).
3. Press
to enter the setting mode. The second line will start to flash.
4. Use
or
to select the desired setting.
5. Press
to confirm the selection.
6. Press
to return the display to the idle mode.
Fig. 3.1.12.-1
Selecting the communication protocol for rear connection
Main Menu
Group Menu
Parameter Menu
MEASUREMENTS
RECORDED DATA
OPERATION
SETTINGS
CONFIGURATION
INFO
CONFIGURATION
FUNCTION TEST/DI
COMMUNICATION
LANGUAGE
MEMORY SETTINGS
FREQUENCY
PASSWORD HMI
TIME
TRIP CIRCUIT SUP
CONFIGURATION
SPA
Confirm
Cancel
ProtocalREF610_B
CONFIGURATION
REAR CONNECTION
REAR PROTOCAL
REAR COM. MODULE
SPA SETTINGS
IEC103 SETTINGS
MODBUS SETTINGS
UNIT ADDRESS
COUNTER
LINE-IDLE STATE
CONNECTION TYPE
IEC 60870-5-103
MODBUS RTU
MODBUS ASCII
COM. MODULE