Warning indication
Warning code
Additional information
Warning
AFL error
33
Analog channel configuration error.
Warning
SMV config error
34
Error in the SMV configuration.
Warning
Comm. channel down
35
Redundant Ethernet (HSR/PRP)
communication interrupted.
Warning
Unack card comp.
40
A new composition has not been
acknowledged/accepted.
Warning
Protection comm.
50
Error in protection communication.
Warning
ARC1 cont. light
85
A continuous light has been detected on
the ARC light input 1.
Warning
ARC2 cont. light
86
A continuous light has been detected on
the ARC light input 2.
Warning
ARC3 cont. light
87
A continuous light has been detected on
the ARC light input 3.
Warning
RTD card error,X130
96
Temporary error occurred in RTD card
located in slot X130.
Warning
RTD meas. error,X130
106
Measurement error in RTD card located in
slot X130.
7.3
Correction procedures
7.3.1
Rebooting the software
1.
Select
Main menu/Configuration/General/Software reset
and press
.
2.
Change the value with
or
and press
.
7.3.2
Restoring factory settings
In case of configuration data loss or any other file system error that prevents the
protection relay from working properly, the whole file system can be restored to the
original factory state. All default settings and configuration files stored in the factory
are restored. Only the administrator can restore the factory settings.
1.
Select
Main menu/Configuration/General/Factory setting
and press
.
2.
Set the value with
or
and press
.
3.
Confirm by selecting
Yes
with
or
and press
.
The protection relay restores the factory settings and restarts. Restoring takes 1...3
minutes. Confirmation of restoring the factory settings is shown on the display a few
seconds, after which the relay restarts.
Section 7
1MRS758754 B
Troubleshooting
110
REC615 and RER615
Operation Manual