GUID-4B27A48C-345A-44A8-A6FB-2FF498AB7307 V1 EN
Figure 45:
Connecting the SMV sender and receivers in IET600
5.
Save and export the SCD file and import it to PCM600.
6.
In PCM600, select
Write to IED
.
If the configuration is updated in a manner that affects the
Conf.Rev
value of SVCB, configurations of both SMV sender and all receivers
must be rewritten from PCM600.
6.4
Bay level configuration
6.4.1
Application configuration of the SMV receiver
The SMV receiver application configuration is done with the Application
Configuration tool in PCM600. TVTR function blocks are used in receiver
application to perform the supervision for the sampled values and to connect the
received analog voltage inputs to the application. When SMVRCV is connected to the
TVTR inputs, the connected TVTR does not physically measure its analog inputs if
they are available in the IED. SMVRCV function block outputs need to be connected
according to the SMV application requirements, typically all three analog phase
voltages connected either to ULTVTR1 or alternatively only a single analog phase
voltage UL1 connected to the ULTVTR2 input. The
VT connection
analog input
setting parameter for phase voltages must be selected accordingly and depending of
the inputs connected either as "Wye" or "UL1". RESTVTR1 input is typically
connected only in case there is measured neutral voltage needed and then available
from the sender.
1MRS757809 C
Section 6
Process bus and IEEE 1588 time synchronization
REC615 and RER615
69
Engineering Guide