GUID-25139ACD-D2B3-4DBC-AA7D-283E7CCA4AF5 V1 EN
Figure 64:
Choosing an SCD file for updating the IED
6.
Select any valid SCL file that is SCD, ICD, CID or IID, and click
Open
from the
file selection dialog box.
IET600 automatically matches IEDs with the same name in IET600 and in the
file.
7.
To import the IED from the file, click
OK
.
GUID-A3ED029A-C586-4086-AEAA-B51E30ADFB31 V1 EN
Figure 65:
Updating the IED
The procedure used in configuring IEC 61850 clients can be used to
create or update any IED, also several IEDs at the same time.
1MRS757809 C
Section 8
Engineering of event reporting with IET600
REC615 and RER615
99
Engineering Guide