Table 17: BU_ Logic input signals
BP internal signal
Designation of binary input signal Description
Block
122205_LOGIC Block
Input for blocking LOGIC function
Binary Input 1
122805_LOGIC Binary Input 1
Logic input 1
Binary Input 2
122810_LOGIC Binary Input 2
Logic input 2
Binary Input 3
122815_LOGIC Binary Input 3
Logic input 3
Binary Input 4
122820_LOGIC Binary Input 4
Logic input 4
Table 18: BU_ Delay input signals
BP internal signal
Designation of binary input signal Description
Block
123205_DELAY Block
Input for blocking of DELAY function
Binary Input
123805_DELAY Binary Input
Input to be delayed
Table 19: BU_CHKI3PH input signals
BP internal signal
Designation of binary input signal Description
Block
124205_CHKI3PH Block
Input for blocking of CHKI3PH
Table 20: BU_ CHKU3PH input signals
BP internal signal
Designation of binary input signal Description
Block
125205_CHKU3PH Block
Input for blocking of CHKU3PH
Table 21: BU_ OCINST input signals
BP internal signal
Designation of binary input signal Description
Block
126205_OCINST Block
Input for blocking of OCINST
3.1.2.4
Binary output signals of BP
GUID-F1D864A5-98AE-4329-8CF0-DEA1F988A246 v1
Table 22: BU_ DIST output signals
BP internal signal
Designation of binary output
signal
Description
Trip CB L1
211105_DIST TRIP CB L1
Circuit-breaker L1 phase trip
This signal is disabled while a blocking
signal is being applied with the exception of
a trip by the backup over-current protection.
Trip CB L2
211110_DIST TRIP CB L2
Circuit-breaker L2 phase trip
This signal is disabled while a blocking
signal is being applied with the exception of
a trip by the backup over-current protection
Trip CB L3
211115_DIST TRIP CB L3
Circuit-breaker L3 phase trip
This signal is disabled while a blocking
signal is being applied with the exception of
a trip by the backup over-current protection.
Trip CB
211305_DIST TRIP CB
General circuit-breaker tripping signal. This
signal is disabled while a blocking signal is
being applied with the exception of a trip by
the backup overcurrent protection.
Table continues on next page
1MRK 505 406-UEN B
Section 3
Signals
Bay protection functions REB500
17
Technical manual
© Copyright 2019 ABB. All rights reserved