1MRK 511 371-UEN
Section 3
IEC 60870-5-103
Communication Protocol Manual, IEC 60870-5-103
17
Distributed busbar protection REB500
The current value of the group header (entry 0) corresponds to the number of
subsystems in the REB500 system software.
Table 17
Directory entry for GIN 0x4000 (header)
COD
Data type
Length
Num
ber
Value / Significance
<10> Description
<1>
OS
8
ASCII
21
1
“Diagnostic information”
<1> Current value
<3> UI
1
1
Number of SW subsystems
All the other entries in this group consist of the following attributes that are needed
to describe a diagnostic event generated by one of the software subsystems.
The status of a diagnostic event is indicated by an ASCII string, which can have
one of the following values:
• “Initializing”
• “Major error”
• “Minor error”
• “Not ready”
• “Ready”
• “Last wish”
• “Shutdown”
• “No
status”
The error code is assigned by the application when the status changes and precisely
describes the cause of the error.
Table 18
Directory entry for GIN 0x40 (xx)
COD
Data type
Length
Num
ber
Value / Significance
<10> Description
<1>
OS
8
ASCII
3
1
“BBP” (example)
<1> Current value
<23>
DATASTRUCTUR
E
29
1
(Includes the following three definitions)
<1> OS8ASCII
12
1
Status
<3>
UI
1
1
Error code
<14>
BINARY
TIME
7
1
Time stamp (CP56Time2a)
The following table gives an example of the ASDU 10 “Generic Data” that is
transferred spontaneously for a diagnostic event.