Attribute name
DATA type
Explanation
M/O/E
OpCntRs
ABB_v4_dSPC
LS Operation counter (reset
command/ status)
E
Controls
Rs
ABB_v4_dSPC
Load shed function reset command
E
SNtw1Rs
ABB_v4_dSPC
Subnetwork 1 reset command
E
SNtw2Rs
ABB_v4_dSPC
Subnetwork 2 reset command
E
SNtw3Rs
ABB_v4_dSPC
Subnetwork 3 reset command
E
SNtw4Rs
ABB_v4_dSPC
Subnetwork 4 reset command
E
Status information
Str
ABB_f_dACD
Load shed function Start
E
Op
ABB_b_dACT
Load shed function Operate
E
3.1.2
PWSACLS
Table 5:
PWSACLS
Attribute name
DATA type
Explanation
M/O/E
ACLS class
ACLS
Contingency load shedding (Slow LS)
M
Data
Common Logical Node Information
Mod
ABB_c_dINC
Mode (Slow load shed function
Enable / Disable / Test command/
status)
M
Beh
ABB_a_dINS
Behaviour (Reflects the mode of the
function)
M
Health
ABB_c_dINS
Health
M
NamPlt
ABB_b_dLPL
Name plate
M
Measured Values
TmElaTrf
ABB_v2_dMV
Elapsed time for Grid trasnformer
E
TmIDMTTrf
ABB_v2_dMV
IDMT Time for Grid transformer
E
MaxDmdS
ABB_v2_dMV
Maximum demand MVA limit setting
E
MaxCurTrf
ABB_v2_dMV
Maximum current for grid transformer
E
Controls
Rs
ABB_v1_dSPC
Load shed function reset command
E
Status information
Str
ABB_f_dACD
Load shed function start
E
Op
ABB_b_dACT
Load shed function operate
E
TrfOvLod
ABB_v1_dSPS
Grid transformer overloaded
E
MaxDmdExc
ABB_v1_dSPS
Max Demand Exceeded (Violated)
E
MaxDmdTm
ABB_v1_dINS
Maximum demand time limit setting
E
Section 3
1MRS757261 C
Logical node extensions
12