Table 52. Three-phase undervoltage protection (PHPTUV)
Characteristic
Value
Operation accuracy
At the frequency f = f
n
±1.5% of the set value or ±0.002 × U
n
Start time
1)2)
U
Fault
= 0.9 x set
Start value
Typical 24 ms (±15 ms)
Reset time
< 40 ms
Reset ratio
Depends of the set
Relative hysteresis
Retardation time
< 35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics
DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,
…
1)
Start value
= 1.0 × U
n
, Voltage before fault = 1.1 × U
n
, f
n
= 50 Hz, undervoltage in one phase-to-phase with
nominal frequency injected from random phase angle
2) Includes the delay of the signal output contact
3) Minimum
Start value
= 0.50 × U
n
,
Start value
multiples in range of 0.90 to 0.20
Table 53. Three-phase undervoltage protection (PHPTUV) main settings
Parameter
Function
Value (Range)
Step
Start value
PHPTUV
0.05...1.20 pu
0.01
Time multiplier
PHPTUV
0.05...15.00
0.05
Operate delay time
PHPTUV
0.040...300.000 s
0.010
Operating curve
type
1)
PHPTUV
Definite or inverse time
Curve type: 5, 15, 21, 22, 23
1) For further reference please refer to the Operating characteristics table
Transformer Protection and Control
1MRS756978 D
RET630
Product version: 1.1
Issued: 2011-05-18
44
ABB