Table 24. Electromagnetic compatibility tests
Description
Type test value
Reference
100 kHz and 1 MHz burst
disturbance test
IEC 61000-4-18
IEC 60255-22-1, level 3
• Common mode
2.5 kV
• Differential mode
1.0 kV
Electrostatic discharge test
IEC 61000-4-2
IEC 60255-22-2
IEEE C37.90.3.2001
• Contact discharge
8 kV
• Air discharge
15 kV
Radio frequency interference
tests
• Conducted, common mode 10 V (rms), f=150 kHz...80
MHz
IEC 61000-4-6
IEC 60255-22-6, level 3
• Radiated, pulse-modulated
10 V/m (rms), f=900 MHz
ENV 50204
IEC 60255-22-3
• Radiated, amplitude-
modulated
10 V/m (rms), f=80...2700
MHz
IEC 61000-4-3
IEC 60255-22-3, level 3
Fast transient disturbance
tests
IEC 61000-4-4
IEC 60255-22-4, class A
• All ports
4 kV
Surge immunity test
IEC 61000-4-5
IEC 60255-22-5
• Communication
1 kV line-to-earth
• Binary inputs, voltage
inputs
2 kV line-to-earth
1 kV line-to-line
• Other ports
4 kV line-to-earth, 2 kV line-
to-line
Power frequency (50 Hz)
magnetic field
IEC 61000-4-8
• 1...3 s
1000 A/m
• Continuous
300 A/m
Transformer Protection and Control
1MRS756978 D
RET630
Product version: 1.1
Issued: 2011-05-18
ABB
25
Содержание Relion 630 Series RET630
Страница 1: ...Relion 630 series Transformer Protection and Control RET630 Product Guide ...
Страница 79: ...79 ...