GUID-C5514DFD-9FE8-4BF7-93D8-14186867D0F8 V1 EN
Figure 283:
Phase-segregated single busbar protection employing high-impedance
differential protection
shows an example for a system consisting of two busbar section coupled with
a bus coupler. Each busbar section consists of two feeders and both sections are provided
with a separate differential protection to form different zones. The formed zones overlap
at the bus coupler.
When the bus coupler is in the open position, each section of the busbar handles the current
flow independently, that is, the instantaneous incoming current is equal to the total
instantaneous outgoing current and the difference current is negligible. The difference
current is no longer zero with a fault in the busbar and the protection operates.
With the bus coupler in the closed position, the current also flows from one busbar section
to another busbar section. Thus, the current flowing through the bus coupler needs to be
1MAC059074-MB A
Section 4
Protection functions
615 series ANSI
559
Technical Manual
Содержание Relion 615 series
Страница 1: ... RELION PROTECTION AND CONTROL 615 series ANSI Technical Manual ...
Страница 2: ......
Страница 39: ...Section 17 Glossary 1181 Table of contents 615 series ANSI 33 Technical Manual ...
Страница 40: ...34 ...
Страница 64: ...58 ...
Страница 210: ...3 19 4 Settings Section 3 1MAC059074 MB A Basic functions 204 615 series ANSI Technical Manual ...
Страница 216: ...210 ...
Страница 884: ...878 ...
Страница 1038: ...1032 ...
Страница 1136: ...1130 ...
Страница 1172: ...1166 ...
Страница 1180: ...1174 ...
Страница 1186: ...1180 ...
Страница 1192: ...1186 ...
Страница 1193: ...1187 ...
Страница 1194: ......
Страница 1195: ......