A070984 V2 EN
Figure 110:
Example coordination of numerical multiple-stage overcurrent protection
4.1.1.8
Signals
Table 211:
51P Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
ENA_MULT
BOOLEAN
0=False
Enable signal for current multiplier
Table 212:
50P Input signals
Name
Type
Default
Description
I_A
SIGNAL
0
Phase A current
I_B
SIGNAL
0
Phase B current
I_C
SIGNAL
0
Phase C current
BLOCK
BOOLEAN
0=False
Block signal for activating the blocking mode
ENA_MULT
BOOLEAN
0=False
Enable signal for current multiplier
Section 4
1MAC059074-MB A
Protection functions
224
615 series ANSI
Technical Manual