ESSXSWI1
POSOPEN
POSCLOSE
OPENPOS
CLOSEPOS
OKPOS
X110_BI6_ES1_OPENED
X110_BI5_ES1_CLOSED
GUID-DEACDD18-8FBF-4AE8-80B1-EF93821D8E51 V2 EN
Figure 109:
Earth switch control logic
The circuit breaker closing is disabled by default, as in case of generator, the closing
of the circuit breaker is done by a special synchronizer device.
The
OKPOS
output from DCSXSWI defines whether the disconnector or breaker
truck is open (in test position) or closed (in service position). This output, together
with the open earth switch and non-active trip signals, activates the close-enable
signal to the circuit breaker control function block. The open operation for circuit
breaker is always enabled.
Connect the additional signals required for the application for opening
of circuit breaker.
CBXCBR1
POSOPEN
POSCLOSE
ENA_OPEN
ENA_CLOSE
BLK_OPEN
BLK_CLOSE
AU_OPEN
AU_CLOSE
TRIP
SYNC_OK
SYNC_ITL_BYP
SELECTED
EXE_OP
EXE_CL
OP_REQ
CL_REQ
OPENPOS
CLOSEPOS
OKPOS
OPEN_ENAD
CLOSE_ENAD
TRUE
X110_BI7_CB_CLOSED
X110_BI8_CB_OPENED
CBXCBR1_EXE_OP
FALSE
FALSE
CBXCBR1_AU_OPEN
GUID-A857DA54-6BF9-4BB1-AD18-99B0387B9015 V2 EN
Figure 110:
Circuit breaker 1 control logic
OR6
B1
B2
B3
B4
B5
B6
O
CB_OPEN_COMMAND
TRPPTRC1_TRIP
CBXCBR1_EXE_OP
GUID-70DB34F4-F3D2-4FAA-908E-DAE8AF653E65 V2 EN
Figure 111:
Signal for opening coil of circuit breaker 1
The configuration includes the logic for generating circuit breaker external opening
command with the relay in local or remote mode.
Connect additional signals for opening of circuit breaker in local or
remote mode, if applicable for the configuration.