![ABB REF630 Скачать руководство пользователя страница 56](http://html.mh-extra.com/html/abb/ref630/ref630_product-manual_3179056.webp)
Table 84. Synchrocheck (SYNCRSYN)
Characteristic
Value
Operation accuracy
At the frequency f = f
n
Voltage: ±1.0% or ±0.002 x U
n
Frequency: ±10 mHz
Phase angle ±2°
Reset time
< 50 ms
Reset ratio
Typical 0.96
Operate time accuracy
±1.0% of the set value or ±20 ms
Measurement functions
Table 85. Three-phase current measurement (CMMXU)
Characteristic
Value
Operation accuracy
At the frequency f = f
n
±0.5% or ±0.002 x I
n
(at currents in the range of 0.01...4.00 x I
n
)
Suppression of harmonics
DFT: -50dB at f = n x f
n
, where n = 2, 3, 4, 5,
…
RMS: No suppression
Table 86. Three-phase voltage measurement (VPHMMXU )
Characteristic
Value
Operation accuracy
At the frequency f = f
n
±0.5% or ±0.002 x U
n
(at voltages in the range of 0.01...1.15 × U
n
)
Suppression of harmonics
DFT: -50dB at f = n × f
n
, where n = 2, 3, 4, 5,
…
RMS: No suppression