![ABB REF630 Скачать руководство пользователя страница 20](http://html.mh-extra.com/html/abb/ref630/ref630_product-manual_3179020.webp)
Table 13. Ethernet interfaces
Ethernet interface
Protocol
Cable
Data transfer rate
LAN/HMI port (X0)
1)
-
CAT 6 S/FTP or better 100 MBits/s
LAN1 (X1)
TCP/IP protocol
Shielded twisted pair
CAT 5e cable with
RJ-45 connector or
fibre-optic cable with
LC connector
100 MBits/s
1) Only available for the external HMI option.
Table 14. Fibre-optic communication link
Wave length
Fibre type
Connector
Permitted path
attenuation
1)
Distance
1300 nm
MM 62.5/125
μm glass
fibre core
LC
<8 dB
2 km
1) Maximum allowed attenuation caused by connectors and cable together
Table 15. X4/IRIG-B interface
Type
Protocol
Cable
Screw terminal, pin
row header
IRIG-B
Shielded twisted pair cable
Recommended: CAT 5, Belden RS-485 (9841-
9844) or Alpha Wire (Alpha 6222-6230)
Table 16. Serial rear interface
Type
Counter connector
1)
Serial port (X9)
Optical ST connector or optical snap-in
connector
1) For future use
Table 17. Degree of protection of flush-mounted IED
Description
Value
Front side
IP 40
Rear side, connection terminals
IP 20
Table 18. Degree of protection of the LHMI
Description
Value
Front and side
IP 42
Feeder Protection and Control
1MRS756380 A
REF630
Product version: 1.0
Issued: 15.09.2009
20