![ABB REF630 Скачать руководство пользователя страница 47](http://html.mh-extra.com/html/abb/ref630/ref630_product-manual_3179047.webp)
Table 67. Circuit breaker failure protection (CCBRBRF)
Characteristic
Value
Operation accuracy
At the frequency f = f
n
±1.5% of the set value or ±0.002 × I
n
Operate time accuracy
±1.0% of the set value or ±30 ms
Table 68. Circuit breaker failure protection (CCBRBRF) main settings
Parameter
Function
Value (Range)
Step
Current value
(Operating phase
current)
CCBRBRF
0.05...1.00 pu
0.05
Current value Res
(Operating residual
current)
CCBRBRF
0.05...1.00 pu
0.05
CB failure mode
(Operating mode of
function)
CCBRBRF
1=Current
2=Breaker status
3=Both
-
CB fail trip mode
CCBRBRF
1=Off
2=Without check
3=Current check
-
Retrip time
CCBRBRF
0.00...60.00 s
0.01
CB failure delay
CCBRBRF
0.00...60.00 s
0.01
CB fault delay
CCBRBRF
0.00...60.00 s
0.01