Remote Monitoring and Control Unit
Technical Reference Manual
Damp heat test, cyclic
according to IEC 60068-2-30
r.h. = 95%, T = 25
°
…55
°
C
Storage temperature tests
according to IEC 60068-2-48
Table 7.1.-10 Standard tests
Insulation tests
Dielectric test
IEC 60255-5
Test voltage
2 kV, 50 Hz, 1 min.
Impulse voltage test
IEC 60255-5
Test voltage
5 kV, unipolar impulses,
waveform 1,2/50
µ
s, source
energy 0.5 J
Insulation resistance
measurements
IEC 60255-5
Insulation
resistance
> 100 M
Ω
, 500 V DC
Mechanical tests
Vibration tests (sinusoidal)
IEC 60255-21-1, class I
Shock and bump test
IEC 60255-21-2, class I
Table 7.1.-11 Electromagnetical compatibility tests
The EMC immunity test level fulfills the requirements specified below
1 MHz burst disturbance
test, class III,
IEC 60255-22-1
common mode
2.5 kV
differential mode
1.0 kV
Electrostatic discharge
test, class III,
IEC 61000-4-2 and
IEC60255-22-2
for contact discharge
6 kV
for air discharge
8 kV
Radio frequency
interference test
conducted, common
mode
IEC 61000-4-6 and
IEC 60255-22-6
10 V (rms),
f = 150 kHz…80 MHz
radiated, amplitude-
modulated
IEC 61000-4-3 and
IEC 60255-22-3
10 V/m (rms),
f = 80…1000 MHz
radiated, pulse-
modulated
ENV 50204
10 V/m, f = 900 MHz
Fast transient
disturbance test
IEC 60255-22-4 and
IEC 61000-4-4
power supply
4 kV
I/O ports
2 kV
Surge immunity test
IEC 61000-4-5 and
IEC 60255-22-5
power supply
4 kV, line to earth
2 kV, line to line
I/O ports
2 kV, line to earth
1 kV, line to line
Power frequency (50 Hz)
magnetic field
IEC 61000-4-8
100 A/m
Voltage dips and
short interruptions
IEC 61000-4-11
30%, 10 ms
60%, 100ms
60%, 1000ms
>95%, 5000ms
Table 7.1.-9
Environmental conditions (Continued)