![ABB REC 523 Скачать руководство пользователя страница 47](http://html.mh-extra.com/html/abb/rec-523/rec-523_technical-reference-manual_2767047.webp)
1MRS750881-MUM
REC 523
47
Remote Monitoring and Control Unit
Technical Reference Manual
psc
Fig. 5.10.-1 Main dialog of the Relay Setting Tool
5.11.
Storing of parameters
When parameter values are changed, the new values take effect immediately.
However, the new parameter values as well as the recorded data are saved in a non-
volatile memory only after they have been stored.
Provided the storing was completed successfully, the information stored in the non-
volatile memory is preserved in the memory also in case of a power interruption.
During the storing procedure, it is not possible to perform software reset or to load
a new project.
The parameters for measuring devices as well as the protocol and
link parameters take effect only after they have been stored and the
device has been reset. Store the parameters via the parameter
Store
, and reset the REC 523 device via the parameter
Software
reset
by opening the Configuration tab and selecting General
subtab. You can use the relay command buttons
Store
and
Reset
in
the Relay Download Tool as well.
The same applies for some communication parameters, that is, the
SPA baud rate, the protocol selection parameters (
Protocol 2
and
Protocol 3)
which can be found by opening the
Communication tab and clicking the General subtab, and the
Command time-out
parameter which is found on the same
subtab.